  • Front view

    • 1 measure module with: 1 fuse block disconnecting switch (3P+N), 1 x 7-positions voltmeter commutator, 1 x 3-digits digital voltmeter, 1 x 4-positions ammeter commutator, 1 x 3 digits Digital ammeter, 2 differential switches (4 pure poles 63A idn 300mA).
    • 1 socket protection module with: 12 magneto-thermic switches (2 poles 16A 6kA/C).
    • 1 output module with: 12 x 16A CEE sockets (1P+N+G).

    Rear view

    • 1 ventilation module.
    • 1 output panel with: 3 x 32A sockets (3P+N+G), 3 diff.  magn. therm. switches (4 poles 32A 6kA/C idn 300mA).
    • 1 input module with: 1 x 63A plug (3P+N+G), 1  magn. therm. switch (4 poles 63A 10kA/C).

    The Power Box is provided with a 63A (3P+N+G) cable mount socket.